Job Recruitment Website - Property management - Can the property front desk share a phone number with the fire control room?

Can the property front desk share a phone number with the fire control room?

You can't. The fire control room is not shared with the duty room, guard, reception room, etc. According to Article 3.4.6 of Code for Design of Automatic Fire Alarm System (GB50 1 16 to 20 13): "It is strictly forbidden to pass through electrical lines and pipelines unrelated to fire control facilities in the fire control room." The fire control room should not be shared with the duty room, guard room and communication room. According to Article 23.2.3 of Code for Electrical Design of Civil Buildings (GB5 1348-20 19), intelligent functional rooms such as security monitoring center can be merged with fire control room. When the fire control room is shared with other functional rooms, it shall comply with the relevant provisions of standards and specifications.