Can the fire pipes for apartment decoration be dismantled?

Fire pipes for apartment decoration cannot be removed. Fire-fighting pipeline belongs to fire-fighting facilities. It is against the fire protection law to modify and dismantle it without permission. However, if the fire department agrees before demolition, it can be demolished, but under normal circumstances, the fire department will not allow it.

How to decorate and hide indoor fire pipes

Ways to hide and beautify the fire pipeline: if the height permits, you can use the pinch plate as the top stop; If the height is not enough, you can color the roof and pipes and hide them visually, which can be used as a distinction and beautification.

Fire fighting pipeline is a pipeline system for fire fighting. There are special requirements for the thickness and material of fire-fighting pipes, and red paint is sprayed to transport fire-fighting water.

Code for installation of fire pipeline

1, casing

(1) When the pipeline passes through the wall, it needs to be jacketed when it passes through the floor. The weld of the pipeline cannot be in the jacketed pipe, and the length of the jacketed pipe cannot be less than the wall thickness.

(2) The floor bushing shall be 50 mm higher than the floor or ground.

2, fire pipeline installation

(1) There shall be no other water facilities on the alarm valve pipeline, and galvanized steel pipes or galvanized seamless steel pipes shall be adopted.

(2) The pipeline of automatic sprinkler system needs to have a certain slope, and the slope direction should be in the drainage pipe or auxiliary drainage pipe. The gradient of main pipe of wet system should not be less than 0.002, and the gradient of water distribution pipe and branch pipe should not be less than 0.005.

(3) The diameter of all water distribution pipes or branch pipes shall not be less than 25mm.

3. Pressure reducing orifice plate and throttling device

(1) needs to be installed on a horizontal pipe section with a diameter of more than 50 mm.

(2) The orifice plate shall be installed on the self-pipe section on the downstream side of water flow turning, and the distance from the bend pipe shall not be less than twice the diameter of the set pipe section.

(3) The length of throttle pipe shall not be less than1.0m.

(4) The main fire water distribution pipe and water distribution pipe shall be marked with red or red rings for easy distinction.