Job Recruitment Website - Property management - What does the fire detection test detect?

What does the fire detection test detect?

The contents of fire detection include: automatic fire alarm system, fire water supply system, indoor fire hydrant system, automatic sprinkler (fog) fire extinguishing system, smoke control and ventilation and air conditioning system, fire door, fire shutter and smoke screen hanging wall, gas fire extinguishing system, new provisions of fire detection in fire protection law and physical tools for fire detection.

The automatic fire alarm system is as follows:

1, to detect the insulation resistance, grounding resistance, system grounding, pipeline installation and protection status of automatic fire alarm system lines;

2. Detect the setting, installation quality, protection radius and distance from surrounding obstacles of fire detectors and manual alarm buttons, and spot check their alarm functions according to the ratio of 30% to 50%;

3. Check the installation quality of the fire alarm controller, the wiring in the cabinet, the setting of protective grounding, the setting of main and standby power supply and its conversion function, and test the function of the controller;

4, fire emergency broadcast sound detection function, manual layer selection and automatic broadcasting, remote control and forced switching functions;

5. Check the setting position and obvious signs of the fire control room, the setting of indoor fire dampers and irrelevant pipelines, and the setting and switching function of double-circuit power supply;

6, detection of fire emergency lighting and evacuation signs setting, illuminance, conversion time and graphic symbols;

7. Check the installation quality of fire-fighting equipment library, wiring in the cabinet, manual and automatic control, and the function of receiving feedback signals from fire-fighting equipment on the screen;

8. Detect the forced landing function of the elevator and the use function of the fire elevator, and cut off the non-fire power supply function and the light display function of the fire floor;

9. Test the fire communication function of the fire control room, various fire equipment rooms and fire hydrant buttons.

legal ground

Regulations on the administration of social fire technical services

Article 7 A fire-fighting technical service institution engaged in the maintenance, inspection and fire safety assessment of fire-fighting facilities shall meet the following conditions:

(a) to obtain the qualification of enterprise legal person;

(two) the construction area of the workplace is not less than 200 square meters;

(3) The basic equipment for fire control technical services and the equipment for maintenance, inspection and fire safety assessment of fire control facilities meet the specified requirements;

(4) There shall be no less than 2 registered fire engineers, among which the first-class registered fire engineers shall be no less than 1 person;

(five) no less than six people have obtained the professional qualification certificate of the national fire control facility operators, including no less than two people with intermediate or above skill level;

(six) a sound quality management and fire safety assessment process control system.