1. A fire technical service agency tested the automatic sprinkler system and checked the design drawings, and found that the sprinkler in the hotel room was ZSTBS80-68, which belongs to ().
election
A. Sprinklers on horizontal side walls
B. Vertical sprinkler
C. Hanging sprinkler
D. Hidden sprinkler
Answer a
2 fire safety key units to carry out fire facilities and equipment inspection. Among the following inspection results, the one that does not meet the current national standard "Code for Acceptance of Fire Extinguisher Configuration in Buildings" (GB50444 1) is ().
election
A. The opening angle of the flip cover in front of the flip fire extinguisher is 90.
B. The opening angle of the open fire extinguisher box door is 175.
C the portable fire extinguisher set in the office is directly placed on the ground.
D the distance between the bottom of the portable fire extinguisher installed on the bracket and the ground is 0. 10m.
Answer a
3. In the topic of making fire-fighting files by key units of fire safety, the following information should be included in the file of "Basic Situation of Fire Safety" ().
election
A. Annual inspection report of automatic fire fighting facilities
B. Unit fire records
C. Records of fire fighting and emergency evacuation planning exercises
D. List of fire fighting equipment of obligatory fire brigade
Answer d
The topic is to check the fire door of an office building. Among the following inspection results, () does not meet the current national standard "Code for Construction and Acceptance of Fire Roller Curtains, Fire Doors and Fire Windows" (GB5087).
election
A the measured lap size of the door leaf and the door frame is 12 mm ~ 15 mm.
B.y The measured gap between the door leaf and the upper frame is 4 mm ~ 6 mm
C the measured gap between the door leaf and the lower frame is 6mm~9mm.
D the measured opening force of the door leaf is 40N~60N.
Answer b
5. A large logistics warehouse plans to prepare a unit fire fighting and emergency evacuation plan. Among the following plans, () does not belong to the plan category specified in the current national standard "Guidelines for the Preparation and Implementation of Fire Fighting and Emergency Evacuation Plans for Social Units" (GB/T383 15).
election
A. Unit master plan
B. Sectoral sub-plans
C. Work breakdown plan
D. Special planning of fire control room
Answer c
6. The security manager of a hotel found many problems in the fire inspection and handled them. Among the following treatment methods, the correct one is ().
election
A. If there are clothes to be dried on the fire pump adapter, fill in the inspection record, report to the leader immediately and ask for instructions for rectification.
B. If a movable billboard is found under the fire shutter, fill in the inspection record and immediately report it to the leader for rectification.
C. If there is a battery car charging in the stairwell, fill in the inspection record and immediately report it to the leader for rectification.
D. If the standby pump of the fire hydrant pump is damaged, fill in the inspection record and immediately report it to the leader for rectification.
Answer d
7. A studio has worked out a fire fighting and emergency evacuation plan. According to the current national standard "Guidelines for the Preparation and Implementation of Fire Fighting and Emergency Evacuation Plans for Social Units" (GB/T383 15), what is not the main content of the plan preparation is ().
election
A. Compilation basis
B. Preparation purpose
C. Scope of application
D. Staffing
Answer d
8. Among the following maintenance and management schemes for automatic sprinkler systems, the one that does not conform to the current national standard Code for Construction and Acceptance of Automatic Sprinkler Systems (GB5026 1) is ().
election
A. Start the automatic sprinkler pump driven by internal combustion engine once a week.
B check the solenoid valve every week and start the test.
C. check the power supply of automatic sprinkler water image once a week.
D, detect the water flow indicator through the terminal water detection device every month.
Answer c
9. An office building, with a building height of 35m, 1 floor above ground and 1 floor underground, with a building area of 3200m2. All buildings are equipped with automatic fire alarm system and automatic fire extinguishing system. The following fire inspection results, does not meet the requirements of the current national standards is ().
election
A the length and width of the front room of the fire elevator are 3m.
B The basement is 4m high, and the fire elevator leads to the basement.
C 1 The fire elevator is set on the ground floor, and an independent fire elevator front room is set.
The fire elevator shaft is separated from the adjacent elevator shaft by a fireproof partition wall with a fire resistance limit of 2.0h
Answer c
10. A building has a flat roof with an outdoor terrace elevation of-0.50m and a building roof elevation of 49.70m. There are supermarkets, restaurants, pharmacies, etc. The first floor of the building, with a building area of 1200m2 and a building area of 1 10m2 ~ 230m2, is separated by a fireproof partition wall with a fire resistance limit of 2.00h and a non-combustible floor of 1.50h, and other floors above the ground are residential buildings. The fire inspection of buildings shall be carried out according to the standard of ().
election
A. A class of high-rise residential buildings
B. Class II high-rise residential buildings
C. A class of high-rise public buildings
D. Type II high-rise public buildings
Answer b
1 1. As a shopping mall, a civil air defense project is divided into four fire zones, A, B, C and D, with construction areas of 1500, 950, 950 and 1000 respectively. Each fire zone is provided with two safety exits, and the safety exit inspection is organized. The following do not meet the requirements (.
election
A in fire zone b, one safety exit is directly connected to the outdoor and the other is directly connected to the evacuation walkway.
One exit of the B.C fire zone goes straight to the outside, and the other goes straight to the A fire zone.
C. one safety exit of fire zone a is directly connected to the outside, and the other safety exit is directly connected to fire zone B.
D. fire zone d, one safety exit is directly connected to the outdoor and the other is directly connected to fire zone B.
Answer c
12. The hotel with a building area of 3000m2 was put into use without the permission of the fire rescue agency. According to the Fire Protection Law of People's Republic of China (PRC), the hotel will face an administrative penalty of ().
election
A. The main person in charge was warned
B. Be ordered to suspend business
C. was fined ten thousand yuan.
D. The main person in charge fined 500 yuan.
Answer b
13. The problem is to check the fire shutter of a building, and there should be a shutter in the middle that does not meet the specifications of * * * * * * ().
election
A. Manually operate the button on the fire shutter controller to control the fire shutter to rise, get off the shelf and stop.
B the electric opening and closing speed of the fire shutter is 8.5m/min.
C. When the deadweight function drops, a fire shutter should be installed, and the falling speed should be 5m/min.
D the maximum noise of the opening and closing operation of the fire shutter is 80db.
Answer b
14. What the terminal water detection device can't detect is ().
election
A. Start function test of alarm valve group
B. Flow and pressure test of the system
C. Start function of pressure switch linkage pump
D. Alarm function test of hydraulic alarm bell
Answer b
15. The following equipment is used to measure the foaming multiple of foam fire extinguishing system ().
election
A. conductivity meter
B. Electronic scales
C. Flowmeter
D. stopwatch
Answer b
16. Title A fire technical service organization carried out fire technical service activities without working experience. According to the Fire Protection Law of People's Republic of China (PRC), the fire rescue agency is ordered to make corrections, and the fire technical service agency is fined more than 50,000 yuan100,000 yuan, and () is also imposed.
election
The person in charge directly responsible for the fire technical service institution and other directly responsible personnel shall be fined 1 10,000 yuan but not more than 50,000 yuan.
B give a warning to the main person in charge of the fire technical service institution.
C. revoke the business license of the fire technical service institution.
D. seal up the office of the fire technical service institution.
Answer c
17. This topic is the debugging of smoke control and exhaust system in a convention and exhibition center. Among the following debugging results, () conforms to the current national standard Technical Standard for Building Smoke Control and Exhaust System (GB5 125 1).
election
A. Two independent fire detectors in the exhibition hall were triggered. After the system sends out a fire alarm signal for 35s, the air supply outlet of the exhibition hall and the corresponding fan are started.
B. Manually open the 1 normally closed air outlet, start the corresponding fan in linkage, and feed back the action signals of the air outlet and the fan to the fire control room.
C. trigger two independent fire detectors in the smoke-proof partition wall of the exhibition hall. After the system sends out the fire alarm signal for 35s, the movable smoke-proof vertical wall in the smoke-proof partition wall drops in place.
D. Manually start a smoke exhaust fan. The fan runs normally, the impeller rotates in the right direction, and the fan runs smoothly within 3.0h without abnormal vibration and noise.
Answer b
18. A fire control technical service institution conducts annual inspection on the liquid in a storage tank. During the foam injection test, it was found that there was no foam within 5 minutes after the foam generator injected liquid, and then white foam was gradually sprayed. The most likely reason for the above situation is ().
election
A. the water in the foam mixture pipeline is not discharged.
B. Exhalation of foam liquid
C. The air inlet of the foam generator is blocked by foreign objects.
D. failure of foam proportional mixer
Answer c
19. the notice titled "opinions on deepening the reform of fire law enforcement issued by the general office of the State Council" (zhong ban zi (2019) No.34) clarifies some specific tasks of the reform of fire law enforcement, and the one that does not belong to the reform tasks stipulated in the opinions on deepening the reform of fire law enforcement is ().
election
A. cancel the qualification license of fire technical service institutions.
B. The fire protection design review and acceptance of construction projects shall be handed over to the housing and urban-rural construction departments by fire rescue agencies.
C. When the public gathering place is put into use, it shall inform and promise the fire safety inspection before business.
D. Relaxing market access restrictions for fire protection products
Answer b
20. A written summary report was prepared for a fire-fighting and emergency evacuation plan drill in a convention and exhibition center. According to the current national standard "Guidelines for Preparation and Implementation of Fire Fighting and Emergency Evacuation Plans for Social Units" (GB/T383 15), what is not included in the summary report is ().
election
A. Assessing the readiness of the exercise
B. Main problems found in the exercise
C. Implementation of the exercise budget
D. Suggestions on the best drill sequence
Answer c
2 1. The pressure spherical tank with a volume of 1000m3 in a chemical plant is protected by water spray fire extinguishing system, which is tested by the fire technical service organization. Among the following test results, () does not meet the current national standard "Technical Specification for Water Spray Fire Extinguishing System" (GB502 19).
election
A the type of water mist nozzle is centrifugal atomizing nozzle.
B the distance between the water mist nozzle and the outer wall of the spherical tank is1.2m.
C, the water mist cones intersect along the latitude direction and are connected along the longitude direction.
D, the nozzle of the water mist nozzle faces the center of the sphere.
Answer b
22. A certain unit has formulated regulations on the management of fire control room. "Regulations" in the following provisions, does not meet the requirements of the current national standards is ().
election
A. a special person is on duty 24 hours a day.
B. Two people are on duty in each shift, of which at least 1 person holds the professional qualification certificate of operators of fire control facilities.
C ensure that the automatic fire alarm system, fire extinguishing system and other linkage control equipment are in normal working condition.
D, ensure that fire water storage facilities such as fire pool and high-level fire water tank have enough water.
Answer b
23. The topic is a garment processing factory building with a height of 27m and six floors above ground. The following fire inspection results, does not meet the requirements of the current national standards is ().
election
A. Set fire lanes along two long sides of the factory building.
B. Fire trucks shall be arranged at intervals of 22M at the climbing operation site.
C. Except for the first floor, a window for fire rescue personnel should be set at an appropriate position on each floor of the external wall of the factory building.
D. The clear height and width of the window on the external wall for firefighters and rescuers to enter are 1.5m and 1.2m respectively.
Answer c
24. The fire rescue agency conducts fire supervision and inspection on a hotel with a building height of 99m. Among the following inspection results, the one that conforms to the Regulations on Fire Safety Management of High-rise Civil Buildings (Order No.5 of the Emergency Management Department) is ().
election
A. the exterior wall billboard is made of flame retardant materials.
B. The food and beverage department shall clean the oil fume exhaust pipeline once every quarter.
C, the food and beverage department set up 1 liquefied petroleum gas cylinder warehouse on the basement.
D. the hotel conducts a fire inspection once a month.
Answer b
25. This topic is to test the automatic fire alarm system of an electric power dispatching building. Among the following test results, () does not meet the current national standard "Fire Protection System" (GB 16806).
election
A. cut off the broadcast information transmission line of the fire emergency broadcasting equipment, and the fire emergency broadcasting equipment sends out a fault signal at 1 10s.
B. Cut off the connecting line between the fire telephone extension and the telephone switchboard, and the fire telephone switchboard sends out a fault signal in 45s.
C, cut off the communication line between the graphic display device in the fire control room and the fire linkage controller, and the graphic display device sends out a fault signal at 95s.
D, cut off the connecting line between the gas fire extinguishing controller and audible and visual alarm, and the gas fire extinguishing controller sends out a fault signal in 80s.
Answer a
26. The problem is that a high-rise building uses pressure reducing valves to supply water to different areas. The fire technical service organization has tested the fire water supply system of the building. Among the following test results, () does not meet the current national standard "Technical Specification for Fire Water Supply and Fire Detection System" (GB50974).
election
A. The proportional pressure reducing valve is installed vertically, and the water flow direction is downward.
B the pressure before the pressure reducing valve is 1.2MPa, and the pressure after the valve is 0.6MPa.
C. Each water supply area in the low area is provided with a set of proportional inversion pressure reducing valve groups.
D the pressure gauge is set in front of and behind the pressure reducing valve, and the dial diameter of the pressure gauge is100 mm.
Answer c
27. A fire technical service agency inspected a large commercial accessory. Among the following inspection results, () does not meet the requirements of the Fire Safety Management Rules for Large Commercial Complex (Trial) C Jixiao (2019) No.314.
election
A. Fast food restaurants with an area of 200m2 use electric heating facilities.
The children's playground on the fourth floor above ground has two separate evacuation stairs.
C. The dining room kitchen on the second floor above ground is arranged by the external wall.
D. The dining room kitchen on the third floor above ground is separated from other parts by firewalls and Class A fire doors.
Answer b
28. According to the current industry standard "Fire Safety Management in Crowded Places" (XF654), the following parts of the shopping mall should be managed according to the requirements of key fire safety parts ().
election
A. Fire fighting equipment warehouse
B. Meeting room
C. General Manager's Office
D. transformer room
Answer d
29. The problem is that a fire technical service organization failed to publicize the fire technical service information in a prominent position in the building after completing the maintenance business of fire facilities in the building. According to the "Regulations on the Management of Social Fire Technical Services" (OrderNo. 136 of the Ministry of Public Security), the fire technical service institutions are ordered to make corrections, and the administrative penalty they face is ().
election
A. be fined 1 10,000 yuan but not more than 30,000 yuan.
B. Be fined more than 5,000 yuan 1 10,000 yuan.
C. be fined more than 50,000 yuan10,000 yuan.
D. be fined up to 5000 yuan.
Answer d
30. When the property right unit of a residential building was conducting a fire inspection, it was found that the shoe cabinet installed by the owner Wang outside the house blocked the fire hydrant box, resulting in the fire hydrant not being used normally. According to the Civil Code of People's Republic of China (PRC), the following statement is wrong ().
election
A. Wang's behavior harmed the legitimate rights and interests of other owners of the residential building.
Property units should take timely and reasonable measures to stop Wang's behavior.
C the property unit ordered Wang to make corrections and imposed a fine on 500 yuan.
D. All owners of residential buildings have the same management right for building fire control facilities.
Answer c
What does the first-class fire engineer take?
Registered fire engineer takes three exams, and the validity of the three exams is kept for three years, which means that he can pass the three exams within three years. These three subjects are fire safety technology practice, fire safety case analysis and comprehensive ability of fire safety technology.
The examination questions of "Fire Safety Technology Practice" and "Comprehensive Ability of Fire Technology" are objective questions. "Multiple-choice question" requires that one of the options best meets the meaning of the question as the answer. "Multiple-choice questions" have two or more options for each question, and the wrong choice does not score; Omitted, 0.5 points will be deducted for each question. Among all multiple-choice questions, there are 80 single-choice questions, each with 1 point; 20 multiple-choice questions, 2 points for each question.
The fire safety case analysis (15) has six subjective questions, and the subjective questions are comprehensive case analysis questions. After 20 16, the questions are 2 multiple-choice questions +4 subjective questions, and the subjective questions are comprehensive case analysis questions. The total scores of the three subjects were 120. Each subject needs to reach more than 72 points (including 72 points).
- Previous article:Brief self-evaluation of property customer service supervisor
- Next article:Can the property arrange parking in front of my garage?
- Related articles
- Summary of work in early March
- Is the property responsible for the loss of electric vehicle battery?
- How does the property inform the owner to dismantle the security door in the corridor?
- How about Foshan Kahang Tianxia Supply Chain Management Co., Ltd.?
- Physical examination requirements of property companies.
- What are the first three bags of property management?
- Complain about whether the telephone, charging pile and money of the property are invested in the blink of an eye, such as one.
- Is it convenient to go to Dalian Country Garden Jing Yun? How should I get there?
- Where is the address of Shanghai Yangpu Fortune Plaza?
- Is the property responsible for elevator failure?