Job Recruitment Website - Property management - Would you like to ask about the setting of fire probe for rolling shutter doors?

Would you like to ask about the setting of fire probe for rolling shutter doors?

Connect the smoke and temperature sensor to the shutter control box, and then add a module to the control box and connect it to the bus-the characteristic is that the smoke and temperature sensor signal automatically starts the shutter control box, and this smoke and temperature sensor is independently connected to the shutter control box without going through the bus. After the shutter door moves, the descending signal will be reported to the fire control center through the bus input module. The disadvantage is that the fire center cannot monitor the fire scene in time. Only when the shutter door moves will the descending signal be reported to the fire center through the module. If the shutter door is not put down for some reason, I don't know. The correct way is to send smoke signal (alarm) and temperature signal (fire confirmation)-the system automatically instructs the linkage module to send a signal to start the shutter door-after the shutter door moves, send a signal to the fire control center. The whole process can monitor the fire scene in time.