Job Recruitment Website - Property management - What are the relevant standards and specifications of fire door monitoring system?

What are the relevant standards and specifications of fire door monitoring system?

Relevant codes and standards are GB29364-20 12 Fire Door Monitor and GB 50 16-20 13 Code for Design of Automatic Fire Alarm System and GB500 16-20 14 Architectural Design.

Article 4.6. 1 of Code for Design of Automatic Fire Alarm System: The linkage control design of fire door system shall meet the following requirements:

1. Alarm signals of two independent fire detectors or a fire detector and a manual fire alarm button in the fire zone where the normally open fire door is located are used as linkage trigger signals for closing the normally open fire door. The linkage trigger signal is sent by the fire alarm controller or the fire linkage controller, and the fire door monitor controls the closing of the fire door in linkage.

2. The opening, closing and fault status signals of each fire door on the evacuation passage should be fed back to the fire door monitor. ?

Extended data:

Code for Design of Automatic Fire Alarm System is divided into 12 chapter and 7 appendices. The main contents include: general rules, terminology, basic provisions, fire-fighting linkage design, selection of fire detectors, setting of system equipment, automatic fire alarm system for residential buildings, combustible gas detection and alarm system, electrical fire monitoring system, system power supply, wiring, automatic fire alarm system for typical places, etc.

Main functions of fire door monitoring system:

Input and output have short circuit protection and detection functions.

Remote on-line monitoring using network

The fire door monitor controls the closing of the fire door after receiving the fire signal.

The fire door monitor has various status indications.

Fire door monitor can quickly diagnose and identify the fault state through buzzer and indicator light.

Fire door monitor has self-checking function.

People's Government of Shouxian County-Interpretation of Code for Design of Automatic Fire Alarm System GB50116-2013

Ministry of Housing and Urban-Rural Development-Statement on Issuing National Standard "Code for Fire Protection in Building Design"