20 19 case analysis of first-class fire engineer: real questions and answers
Company A (the property right unit of a warehousing and logistics park, legal representative: Zhao) leased warehouses 12, 22, 32, 42 and 52 to Company B (legal representative: Qian), and Company B stored barrels of lubricating oil and solvent oil in the warehouse, and Company A entrusted Company C (fire technical service agency, legal representative:) to build the above warehouses.
2065438+On April 8, 2009, the staff members of the fire rescue agency, Li and Wang, inspected the warehouse used by Company B and found: 1. Main pump and standby pump of indoor fire hydrant are damaged; 2. The linkage controller of automatic fire alarm system is set in manual state, and the start switch of fire pump control cabinet of automatic sprinkler system is also set in manual control state; 3. Some personnel on duty in the fire control room work without a license; 4. There is no regular inspection and testing record for the electrical lines and equipment in the storage place, and there is a phenomenon of long-term overload operation and line insulation aging; 5.5 The two evacuation exits on the east and north sides of the warehouse are blocked by a large number of stacked cartons and parcels; 6. Two fire shutter damage rings. The staff of the fire rescue agency immediately issued a legal document, ordered * * * to make corrections, and made corrections within a time limit until April 28th, and was given administrative punishment according to law. During the review on April 29th, it was found that in addition to the above items 5 and 6, the problems in items 1, 2, 3 and 4 still existed: colleagues found that all items were qualified in the internal fire inspection, inspection records and annual inspection records of fire protection facilities issued by Company C, and Li and Wang issued relevant legal documents according to the above situation.
On April 30th 17: 29, Zheng and Zhou, the personnel on duty in the fire control room of Company B, heard the alarm signal, indicating that the smoke detector in Warehouse No.5 1 area gave an alarm, but Zheng and Zhou, the personnel on duty in the fire control room, did nothing after hearing the alarm. Wu Mou, an employee, heard the fire alarm and found smoke in the warehouse. He immediately called 1 19 to call the police. After the local fire broke out, the fire was put out at 23: 50 that day.
The fire caused three deaths and the direct economic loss was about 10944 million yuan. The comprehensive analysis of the accident investigation team found that: 5. The electrical circuit in the west wall of the warehouse broke down, and the generated high-temperature arc ignited the insulation materials of the circuit. The burning insulation materials fell and were introduced into the lubricating oil cartons and gravel plastic lake film packaging materials stored under the fire, and then spread into a disaster.
According to the above materials, answer the following questions (*** 18, 2 points for each question. Two or more options in each question meet the meaning of the question, and there is at least one mistake. Wrong choice, this question does not score; Choose less, 0.5 points will be deducted for each choice)
1. According to the Fire Protection Law of People's Republic of China (PRC), the fire safety responsibility that Party A should perform is ().
election
A before the warehouse is put into use, it shall apply to the local fire rescue organization for fire safety inspection.
B. Implement the fire safety responsibility system, and formulate the fire safety system according to the use nature of the warehousing and logistics park.
C allocate fire-fighting facilities and equipment according to national standards, industry standards and local standards.
D. Conduct a comprehensive inspection of building fire protection facilities at least once a year to ensure that they are in good condition and effective.
E. organize fire prevention inspection to eliminate fire hazards in time.
Answer ACDE
2. Title According to the Regulations on Fire Safety Management of Organs, Organizations, Enterprises and Institutions (Order No.61of Public Relations Department), the legal representative of Company B, Tian Mou, should perform the following fire safety duties ().
election
A. Understand the company's fire safety situation, and ensure that the fire safety complies with regulations.
B coordinate the fire control work with the company's warehouse management and other activities, and approve the implementation of the annual fire control work plan.
C. Non-governmental organizations should formulate fire safety systems and operating procedures to ensure fire safety, and supervise and urge their implementation in 2008.
D. Organize the formulation of fire fighting and emergency evacuation plans and implement drills according to the actual situation of the Company.
E organize and implement the maintenance of the company's fire-fighting facilities, fire-fighting equipment and fire safety signs to ensure that they are in good condition and effective.
Answer ABD
3. According to the Regulations on Fire Safety Management of Organs, Organizations, Enterprises and Institutions (Order No.61), the statement about the division of fire safety responsibilities between Company A and Company B is correct ().
election
A. The emergency rooms provided by Company A to Company B that meet the fire safety requirements.
B party a and party b shall specify the fire safety responsibilities of all parties in the contract according to relevant regulations.
C. Company B shall perform fire safety duties within the scope of its use and management.
D. The public fire truck passage in the park is managed by Company B or the unit entrusted by Company B..
E evacuation facilities in the park and other building fire-fighting facilities related to public fire safety shall be managed by Party B or the unit entrusted by Party B..
Answer ABC
4. The statement about the fire control work of India and Company B is correct ().
election
A. Zhao is the person in charge of fire safety in company A.
B. Money shall provide necessary funds and organizational guarantee for Party A's fire safety.
C.B company shall set up or determine the centralized management functional department of the company's fire control work.
D. Qian is the fire safety manager of company B.
Company E.A and Company B shall establish volunteer fire brigades and other fire control organizations as required.
Answer ACE
5. Let's discuss the emergency steel case of Company B: how to do it, how to make it bigger, and how to practice it in teaching and business. Correct, political network ().
election
The powerful weaving organization in the emergency plan of company A.B is divided into the fire action department. Don't be a guide station, protect the man-machine and the first worker with safety protection.
B. Before the fire drill, Qianmou informed the gold barrier keeper in advance in the drill flow chart to learn to cooperate with the logo.
C skyfire, when you get wet, you must set it in front of company B and other countries, so it is easy to prevent fire.
D. after the mid-year regulations were produced, Gende and Physical Education felt that the company had the ability to prevent integration.
Answer ABC
6. Problem stem In order to strengthen the management and fire alarm handling ability of the fire control room in the warehousing and logistics park, the following corrective measures are correct for the problems raised by the staff of the fire rescue agency ().
election
A.A Company has defined the responsibilities of the centralized departments, managers and their staff for the maintenance and management of building fire-fighting facilities and fire-fighting control rooms to ensure the normal operation of building fire-fighting facilities.
B the fire control room of each unit shall be on duty 24 hours a day, with no less than 2 personnel in each shift, and the personnel on duty shall hold the professional qualification certificate for the operation of the fire control room.
C under normal working conditions, the automatic fire alarm system is not in an automatic state.
D. If the fire control facilities are found to be faulty during duty, they shall be repaired in time. If it is really necessary to stop using the fire protection system, effective measures shall be taken to ensure fire safety and approved by the person in charge of fire safety of the unit.
E. After receiving the alarm information, the personnel on duty in the fire control room should immediately start the function of silencing and resetting, and confirm it in the fastest way.
Answer ABC
7. Title According to "People's Republic of China (PRC) Fire Protection Law" and "Regulations on the Management of Social Fire Protection Technical Services" (DecreeNo. Ministry of Public Security 136), the legal responsibility that should be investigated for Company C is ().
election
A. It shall be ordered to make corrections, and a fine of 1 10,000 yuan but not more than 20,000 yuan shall be imposed, and a fine of 1 1000 yuan but not more than 5,000 yuan shall be imposed on the directly responsible person in charge and other directly responsible personnel.
B order it to make corrections, impose a fine of not less than 20,000 yuan but not more than 30,000 yuan, and investigate the responsibilities of the directly responsible person in charge and other directly responsible personnel.
A fine of not less than one thousand yuan but not more than five thousand yuan shall be imposed.
C shall be ordered to make corrections, and be fined not less than 50,000 yuan but not more than 100,000 yuan, and the directly responsible person in charge and other directly responsible personnel shall be fined not less than 10,000 yuan but not more than 50,000 yuan.
D. If the circumstances are serious, the original licensing authority shall order it to stop practicing or revoke the corresponding qualification according to law.
E. If the case constitutes a crime, criminal responsibility shall be investigated according to law.
Answer CD
8. The topic is responsible for those who can cause disasters, and criminal coercion should be made with substances for those who participate in crimes ().
election
Zhao from A.A company
B. Qian Mou of Company B
Sun Mou of C.C. Company
D. Fire rescue agencies Li and Wang
Zhou and Zheng from E.B. Company.
Answer AB
9. The problem stems from the fact that in order to seriously learn the lessons of this fire accident, Company A requires all units in the park to seriously carry out fire inspection, patrol and fire hazard rectification. Among the following specific rectification measures, the correct one is ().
election
A. Each unit shall organize a fire inspection every quarter to eliminate fire hazards in time.
B fire inspection shall include the on-the-job situation of various key personnel to ensure foolproof.
C. check the fire control facilities of the park buildings every six months.
D. Regularly inspect and test the electrical lines and equipment in the storage places in the park, and replace the electrical lines with aging insulation.
E, before the fire hazards are eliminated, all units should strictly implement preventive measures to ensure fire safety.
Answer BDE
Case (3)
A furniture factory has a building area of 13000m2, a cast-in-place reinforced concrete frame structure (minimum section size of 400mm*500mm, protective layer thickness of 20mm) and a clay brick wall enclosure. The fireproof limit of incombustible floor is not less than 1.50h, the load-bearing members of the roof are made of steel mesh with fireproof limit not less than 1.00h, the non-upper roof is made of colored steel sandwich panel, and the core material is rock wool (mass 58kg/m2). See figure 1 for the building and general layout.
The furniture workshop is equipped with a semi-underground intermediate warehouse with a building area of 300m2, and the paint and thinner mainly composed of toluene and xylene can be stored for no more than one day and night. A 500㎡ painting workshop is set up in the southeast corner of the second floor of the furniture factory, which is adjacent to the external wall. It adopts a closed painting process and is separated from other parts by a fireproof partition wall. A 1 Class A fireproof door is set up, which will automatically close in case of fire. The middle warehouse and paint area adopt anti-static and spark-free ground, and the outer wall is provided with vents. According to the regulations, all electrical equipment should be explosion-proof. A 500m2 power distribution room is arranged in the northwest corner of the first floor (the oil loading capacity of each equipment is 65kg), and it is separated from other parts by a fireproof partition wall. The safety evacuation of furniture production workshop and the setting of building fire protection facilities meet the requirements of fire protection standards.
?
According to the above materials, answer the following questions (***20 points)
1. What is the fire resistance rating of this furniture factory? The fire hazard categories of workshop, intermediate warehouse, painting section and power distribution room in workshop are pointed out respectively.
2. How many meters should the fireproof distance between dry furniture workshop and office building, toy workshop, bottled liquid ammonia warehouse and electrolytic brine workshop be less than?
3. How many fire zones should each floor of dry furniture production workshop be divided at least? What are the problems in the plane layout and explosion-proof measures of the factory building?
4. What explosion-proof measures should be taken to set up pipes, ditches and sewers in the dry paint section?
5. Calculate the pressure relief area of the painted part (the aspect ratio of the painted part
Case (4)
A complex building has underground 1 floor, 5 floors above ground and 6 floors locally. The elevation of the first floor indoor terrace is 0.000 m, the elevation of the outdoor terrace is -0.600m, and the roof is flat. The building is a cast-in-place reinforced concrete frame structure, with the fire resistance of columns of 5.00h and beams, floors and evacuation stairs of 2.50h h. The walls of firewalls, stairwells and elevator shafts are all made of aerated concrete blocks, with the fire resistance of 5.00 h. The partition walls on both sides of the evacuation walkway and the room partition walls are made of steel keels, and the fire-proof paper stone backboards (filled in the middle 100mm thick sound insulation glass silk wool) are nailed on both sides, with the fire resistance limit. Ceiling adopts wooden ceiling keel nail 10mm thick gypsum board, and the fire resistance limit is 0.25h h.
Except the ground floor height of the complex building is 4.2m, the heights of other floors are 3.9m, with a construction area of 960m2 and a top floor construction area of 100m2. The purpose and number of people on each floor are: the first floor is the equipment room and bicycle garage, with 30 people; The first floor is the hall, kitchen and dining room, 100 people; On the second floor is a restaurant with 240 people; On the third floor is the ballroom (the number of people needs to be counted); The fourth floor is a gym, 100 people; The fifth floor is the children's dance training center, 120 people. There are two safety exits on the ground floor and three on the underground floor, one of which is a bicycle exit.
Stairs 1 and 2 are located in the same position on each floor, and open stairwells are adopted. The clear width 1.50m of Class A fire doors (without FM 1) is set at the entrance of the stairwell on the basement level, and the opening direction is along the direction of people entering the basement level.
The three-story plan of the comprehensive building is shown in Figure 2. In the drawing, M 1 and M2 are wooden sound-proof doors with clear widths of 1.30m and 0.90mM4 are ordinary wooden doors, with clear widths of 0.90mJXM 1 and JXM2 being Class C fire doors with a width of 0.60m.
The whole building is equipped with central air conditioning system, wet automatic sprinkler system and other fire-fighting facilities, and all fire-fighting systems are set up in accordance with the requirements of national fire-fighting technical standards and are complete and easy to use.
According to the above materials, answer the following questions (***24 points)
1. Calculate the building height of the complex building and determine the building category of the complex building.
2. Judge whether the fire resistance rating of the complex building meets the specification requirements and explain the reasons.
3. Question whether the fire partition of the comprehensive building meets the requirements of the code, and explain the reasons.
4. Calculate the minimum total clear width of the external doors on the first floor and the minimum total clear width of the evacuation stairs on the second floor.
5. The problems existing in the plane layout and fire separation of the complex building are pointed out.
6. The stem points out the problems in the stem and safe evacuation in Figure 2.
Case (5)
A high-rise commercial complex has two floors underground, 30 floors above ground and one to five floors above ground for shopping malls. According to the requirements of the code, automatic fire alarm system, emergency lighting and evacuation indication system, smoke control system and other building fire protection facilities are set up. The owner entrusts the fire control technical service institution to test the fire control facilities. The test process and results are as follows:
1, function detection of automatic fire alarm facilities
Twenty smoke detectors were randomly selected at the scene, and the alarm function was tested by adding smoke. Only 1 did not give an alarm, only 1 did not display the alarm position information correctly, and the rest 18 had normal alarm function.
2. Detection of linkage control function of fire alarm and fire emergency broadcast.
The linkage controller is set to automatic working mode. Smoke on the eighth floor triggers 1 smoke detector alarm, and the acousto-optic alarm on the eighth floor starts, and smoke on the eighth floor triggers another 1 smoke detector alarm. Fire emergency broadcasts on the seventh, eighth and ninth floors are started at the same time, and alarm and evacuation information are also broadcast.
3. Detection of linkage control function of smoke exhaust system
Set the linkage controller to the automatic working mode, press the 1 alarm button on the 28th floor corridor, and the controller outputs the start signal of the smoke exhaust valve on this floor. It was found that the smoke exhaust valve was opened and the corresponding smoke exhaust fan was not started. Press the manual start button on the field electric control box of the smoke exhaust fan, and the smoke exhaust fan will start normally.
4. Functional detection of fire emergency lighting and evacuation indication system
On the first floor of the commercial complex building, two detectors of the simulated fire alarm system alarm, and the fire alarm controller sends out a fire alarm output signal. When the ground evacuation indicator light of the commercial complex building is not lit in an emergency, the emergency lighting controller is manually operated for emergency start, and all emergency lighting and evacuation indicators are turned into emergency working state.
According to the above materials, answer the following questions (***20 points)
1. What is the main reason why the smoke sensor of this commercial complex doesn't give an alarm? How to solve the problem that the alarm position information is incorrect?
2. Question stem According to the current national standard Code for Design of Automatic Fire Alarm System (GB50 1 16), is the linkage control function of fire alarm and fire emergency broadcast of this commercial complex normal? Why?
3. According to the current national standard Code for Design of Automatic Fire Alarm System (GB50 1 16), is the linkage control function of smoke exhaust system in commercial complex normal? Why? What is the main reason why the linkage control smoke exhaust fan does not start?
4. Which type of sparse indicator light should be selected for the commercial complex? Is the function of fire emergency lighting and evacuation indication system normal? Why?
5. What is the reason why the ground evacuation indicator light of the commercial complex building did not light up during the functional test of the fire emergency lighting and evacuation indication system?
Case (6)
A financial data center building in Northeast China has four floors with a total construction area of 1 1200m2. The first floor is high and low voltage distribution room, fire pump room, fire control room, office, etc. The second floor is the recording (paper) media library, the third floor is the recording (paper) media library (backup) and the important customer file room, and the fourth floor is the data processing room. The second and third floors are equipped with pre-action automatic sprinkler systems, using 896 sprinklers (including 365,438 ceilings, 3 16 ceilings and 264 others). The high and low voltage power distribution room, data processing room and communication room are protected by combined distribution IG54 1 mixed gas fire extinguishing system. IG54 1 96 fire extinguishing agent storage bottles with specifications of 90L in the mixed gas fire extinguishing system, with indoor temperature of about 5℃.
Fire technical service agencies found that:
1. The pre-action automatic sprinkler system is equipped with two pre-action alarm valve groups, which are considered to be in line with the relevant provisions of the current national standard Code for Design of Automatic Sprinkler Fire Extinguishing Systems (GB50084) by the personnel of fire technical service institutions.
2. The pre-action automatic sprinkler system is in paralysis. According to the owner's report, the air pump control box of the system displays low-pressure alarm for a long time, resulting in the air pump running all the time. All water supply and gas supply pipelines, components and interfaces have been subjected to water pressure test and air tightness inspection for many times, and the air tightness of the air pump has been checked for many times, and no problems have been found, so the system has to be shut down.
3. The lower part of the doors and windows of the high and low voltage distribution room is a louver as a pressure relief port.
4.IG54 1 The pressure gauge for fire extinguishing agent storage in gas fire extinguishing system is 13.96MPa. The personnel of fire technical service institutions think that the pressure is low, and there may be a slow leakage of fire extinguishing agent.
According to the above materials, answer the following questions (***20 points).
1. How many pre-action alarm valve groups should the pre-action automatic sprinkler system be equipped with? Why?
2. When testing the pre-action automatic sprinkler system, which equipment or components should be tested at least besides the air pump?
3. List the reasons that may cause the pump control box of pre-acting automatic sprinkler system to display low-pressure alarm for a long time and the air pump keeps running.
4. Question: Does the pressure relief port of high and low voltage power distribution room meet the requirements of standards and specifications? Briefly explain why.
5. Is it correct for the personnel of fire technical service organization to think that the storage pressure of fire extinguishing agent in IG54 1 gas fire extinguishing system is low and there may be slow leakage of fire extinguishing agent? Briefly explain why.
?
- Previous article:What is the telephone number of Hanzhong Shangda Yujingyuan Marketing Center?
- Next article:How to complain about poor property service?
- Related articles
- Treatment of College Student Village Cadres in Xiantao City
- How about Tangshan Zheng Hao Human Resources Service Co., Ltd.
- Which property is Yancheng Fenglinfu?
- How to explain the advantages of real estate lots
- Excellent maintenance workers Part 3
- How about Yulin Jin Hui Property Management Co., Ltd.
- Jiamusi Chang 'an Community Property Grade
- Mid-Autumn Festival is suitable for property activities.
- What is the telephone number of the sales office in Tong Yuan, the provincial capital?
- A comparison between the first city of Shenghui in Dalian and the new hope home