Provisions on the allocation of fire extinguishers in commercial places?

According to the relevant requirements, the following provisions are made:

First, the service life of the newly purchased fire extinguisher

1, dry powder fire extinguisher

Accumulator type: maintenance should be carried out after five years from the factory or when the pressure pointer points to the red area;

Type of gas cylinder: maintenance shall be carried out five years after delivery or when the total weight of gas in the gas cylinder decreases 10g.

Type of cart: maintenance after delivery for five years.

2, carbon dioxide fire extinguisher

Maintenance should be carried out five years after leaving the factory or after each use.

When the total weight of fire extinguishing agent is reduced by more than 50 grams, it should be maintained. Type of cart: it should be maintained five years after delivery or after each use. The wheeled foam extinguisher should be maintained after two years of use.

Clear water fire extinguisher. Water film fire extinguishers should be maintained after leaving the factory for three years.

Second, the service life of the fire extinguisher after maintenance

1, stored-pressure dry powder fire extinguisher: it should be repaired after two years of maintenance.

The pressure pointer pointing to the red area should be repaired;

2. Gas cylinder dry powder fire extinguisher: it should be repaired again after two years of maintenance.

When the weight of gas in the gas cylinder is reduced by more than 10g, maintenance shall be carried out.

3, carbon dioxide fire extinguisher

Maintenance should be carried out after two years of maintenance.

When the total amount of extinguishing agent is reduced by more than 50g, it should be repaired again.

Type of cart: it should be maintained five years after delivery or after each use. Cart-type foam extinguisher should be replaced with chemicals every year after maintenance.

Clear water fire extinguisher. Water film fire extinguishers should be maintained every two years after maintenance.

Third, the retirement age of fire extinguishers.

1, dry powder fire extinguisher

The pressure storage portable dry powder fire extinguisher should be scrapped after leaving the factory 10. The portable dry powder fire extinguisher with gas storage should be scrapped after leaving the factory for 8 years. Cart-type dry powder fire extinguishers should be scrapped after leaving the factory 10.

2. Carbon dioxide fire extinguishers should be scrapped after leaving the factory 12 years.

When the residual deformation rate of gas cylinders is greater than 6%, the wheeled foam extinguisher should be scrapped for 8 years, the clean water portable fire extinguisher should be scrapped for 6 years, and the water film portable fire extinguisher should be scrapped for 6 years.

The cylinder body is seriously corroded (paint falls off in a large area, and the corrosion area exceeds one third of the total area of the cylinder body) or the joint part, and the bottom of the cylinder body is seriously corroded, so it should be scrapped.

The instructions on the fire extinguisher fall off or are seriously damaged (to the extent that the use method cannot be explained, it is suitable for extinguishing material fires).

Third, the management of fire extinguishers

1. The competent department of fire-fighting equipment shall establish the management account of fire-fighting equipment of the unit, and the account shall indicate the specifications, models, quantities, storage locations, release dates and validity periods of fire-fighting equipment. Reflect the purchase quantity, maintenance type, quantity, time, production and maintenance unit, component configuration, manager and person in charge.

2, the competent department of fire equipment to draw fire equipment distribution map, clear the storage location of fire equipment. All grass-roots units shall report to the competent department in time if there is any change in fire fighting equipment.

3. The competent department shall inspect the use and storage of fire-fighting equipment every quarter to ensure that the fire-fighting equipment is in good condition, the accessories are complete, and the date in the tank and the service period of the gas cylinder are within the validity period.

4. The location of fire extinguishers should be no more than 1.5m at the top, no less than 0 15m at the bottom, and no more than 2 and no more than 5 at each place, which is convenient for taking.

5. The person in charge of each post is responsible for the daily maintenance of the fire extinguisher, and it is not allowed to be stored in the environment of overtemperature, sun and rain, and it is not allowed to be blocked by sundries or inconvenient to take and put.

6, after the maintenance of the fire extinguisher should fill in the maintenance record in time, and the appropriate identification on the label of the fire extinguisher. If there is no maintenance label or the expiration date is not indicated, it is considered as not maintained.

7. Relevant personnel in each position must learn to use fire extinguishers correctly and master relevant fire fighting knowledge. The fire department is responsible for the training of relevant personnel. Establish relevant records.