The effective volume of high-level fire water tank of temporary high-pressure fire water supply system should meet the requirements of initial fire water consumption.

And shall meet the following requirements:

1, a kind of high-rise public building, should not be less than 36m3, but not less than 50m3 when the building height is greater than 100m, and not less than100m3 when the building height is greater than 150m; ;

2. Multi-storey public buildings, Class II high-rise public buildings and Class I high-rise residential buildings should not be less than 18m3, and when the height of Class I high-rise residential buildings exceeds 100m, it should not be less than 36m3;;

3. Class II high-rise residential buildings shall not be less than12m3; ;

4, the building height is greater than 2 1m, multi-storey residential, should not be less than 6 m3;

5. When the design flow of indoor fire water supply for industrial buildings is less than or equal to 25L/s, it should not be less than 12m3 and18m3; When it is greater than 25L/s;

6. Store buildings with a total construction area of more than 10000m2 and less than 30000m2 should not be less than 36m3, and store buildings with a total construction area of more than 30000m2 should not be less than 50m3. If it is inconsistent with the provisions of Article 1, the larger value shall be taken.